Board-X Ups Online 6Kva 5400W Internal Battery 16X 12V/7Ah
zoom_out_map
chevron_left chevron_right

Board-X Ups Online 6Kva 5400W Internal Battery 16X 12V/7Ah

-Power: 5400W
-Output: Online double conversion with full digital control
-Frequency: 50/60HZ
-Voltage: 220V
-Battery: 6x 12V/7AH Sealed Inside

Create Account To View Prices!

By buying this product you can collect up to 730 loyalty points. Your cart will total 730 points that can be converted into a voucher of $7.30.


 

Best Price Guaranteed

 

Delivery all over Lebanon

 

Daily Updated Website

Capacity 6000VA/ 5400W 10000VA/ 9000W
INPUT  
Nominal voltage 208/220/230/240Vac
Input voltage range 110~286Vac
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
Bypass voltage range Max.voltage:230~264Vac
Min.voltage:176~220Vac
OUTPUT  
Output voltage 208/220/230/240Vac
Power factor 0.9
Voltage regulation ±1%
Output frequency Line Mode ±10% of the rated frequency
Bat. Mode (50/60±0.1%)Hz
Crest factor 3:01
Harmonic distortion (THDv) ≤2% Linear load
≤5% Non linear load
Transfer time AC mode to Bat.Mode 0ms
Inverter to Bypass 5ms (Typical)
Output waveform Pure Sinewave
Overload Line Mode Load≤105% long time running; ≤125% last 10min; ≤130% last 30s; >130% turn to bypass mode immediately
Bypass Mode 40A (Breaker) 63A (Breaker)
Efficiency 93.50%
BATTERY
Battery voltage 192/216/240Vdc (Adjustable) ,without neutral 240Vdc 192/216/240Vdc (Adjustable) ,without neutral 240Vdc
Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Typical recharging time 6~8 hours (to 90% of full capacity)
Charging current 1A (Standard unit); Long run unit Max.current 8A (Charging current can be set according to battery capacity)
INDICATORS
LED display Line mode,Bat.mode,ECO mode,Bypass mode,Battery low voltage,Overload & UPS fault
LCD display Input voltage,Input frequency,Output voltage,Output frequency,Load percentage,
Battery voltage,Inner temperature& Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continously beeping
PHYSICAL
Dimension W x D×H (mm) H:191 x 460 x 337 ; S:191 x 460 x 720 (With wheel)
Net weight (kg) 12 69.5 13.5 71
ENVIRONMENT  
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m,derating required when>1500m
Noise level <55db at 1 Meter <58db at 1 Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
UPS l19
Data sheet
Output Capacity
5400W
Battery
Internal